Equivalence of direct radiation (EDR) is a standardized comparison method for estimating the output ability of space-heating radiators and convectors. Measured in square feet, the reference standard for EDR is the mattress radiator〔http://www.heatinghelp.com/newsletter.cfm?Id=157 mattress radiator〕 invented by Stephen J. Gold in the mid 19th century. One square foot of EDR is able to liberate 240 BTU per hour when surrounded by air and filled with steam of approximately temperature and 1 psi of pressure. EDR was originally a measure of the actual surface area of radiators. As radiator (and later convector) design became more complicated and compact, the relationship of actual surface area to EDR became arbitrary. Laboratory methods based on the condensation of steam allowed for very accurate measurements. While now somewhat archaic, EDR is still computed and used for sizing steam boilers and radiators, and for modifying and troubleshooting older heating systems using steam or hot water. However, In a hot water system, one square foot of EDR is able to liberate 170 BTU per hour, depending on the temperature of the water.〔http://www.colonialsupply.com/resources/radiator.htm〕 == References == * * 抄文引用元・出典: フリー百科事典『 ウィキペディア(Wikipedia)』 ■ウィキペディアで「Equivalence of direct radiation」の詳細全文を読む スポンサード リンク
|